Mitsubishi Electric MELSEC-Q series User Manual page 147

Programmable controller current transformer input module
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

Item
Conversion enable/disable setting
Averaging process setting
Basic setting
Average time/Average number of
times/Moving average/Time constant
settings
Sampling cycle setting
Process alarm warning output setting
Process alarm upper upper limit value -32768 to 32767 (default value: 0)
Process alarm upper lower limit value
Process alarm lower upper limit value
Warning output
Process alarm lower lower limit value
function
Rate alarm warning output setting
Rate alarm warning detection period
Rate alarm upper limit value
Rate alarm lower limit value
Input signal error
Input signal error detection setting
detection
Scaling enable/disable setting
Scaling function
Scaling upper limit value
Scaling lower limit value
Input range setting
Input range setting
Dropout detection setting
Dropout setting
Dropout value
Setting value
0: Enable
1: Disable (default value)
0: Sampling Processing (default value)
1: Time Average
2: Count Average
3: Moving Average
4: Primary Delay Filter
Time
40 to 5000ms (default value: 0)
Average
Count
4 to 500 Times (default value: 0)
Average
Moving
2 to 1000 Times (default value: 0)
Average
Primary
10 to 10000ms (default value: 0)
Delay Filter
0: 10ms/8CH (default value)
1: 20ms/8CH
2: 50ms/8CH
3: 100ms/8CH
0: Enable
1: Disable (default value)
-32768 to 32767 (default value: 0)
-32768 to 32767 (default value: 0)
-32768 to 32767 (default value: 0)
0: Enable
1: Disable (default value)
10 to 5000ms (default value: 0)
-3276.8 to 3276.7%/s (default value: 0)
-3276.8 to 3276.7%/s (default value: 0)
0: Enable
1: Disable (default value)
0: Enable
1: Disable (default value)
-32000 to 32000 (default value: 0)
-32000 to 32000 (default value: 0)
0: Factory Default Range 0 to 5AAC (default value)
1: Factory Default Range 0 to 50AAC
2: Factory Default Range 0 to 100AAC
3: Factory Default Range 0 to 200AAC
4: Factory Default Range 0 to 400AAC
5: Factory Default Range 0 to 600AAC
16: User Range 0 to 5AAC
17: User Range 0 to 50AAC
18: User Range 0 to 100AAC
19: User Range 0 to 200AAC
20: User Range 0 to 400AAC
21: User Range 0 to 600AAC
0: Enable
1: Disable (default value)
1 to 10000 (default value: 50)
CHAPTER 8 VARIOUS SETTINGS
Reference
Page 35,
Section 4.3
Page 36,
Section 4.5
Page 35,
Section 4.4
Page 51,
Section 4.10
(1)
Page 53,
Section 4.10
(2)
Page 42,
Section 4.6
Page 48,
Section 4.9
Page 34,
Section 4.2
Page 47,
Section 4.8
145
8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents