4.3

Conversion Enable/Disable Function

Set whether to enable or disable the digital conversion for each channel.
(1) Setting procedure
1.
Set Enable (0) or Disable (1) to Conversion enable/disable setting (Un\G0).
2.
Turn on then off Operating condition setting request (Y9).
4.4

Sampling Cycle Switching Function

A sampling cycle can be selected from one of the following.
• 10ms/8CH
• 20ms/8CH
• 50ms/8CH
• 100ms/8CH
(1) Setting procedure
1.
Set a sampling cycle to Sampling cycle setting (Un\G26).
Sampling cycle setting (Un\G26)
2.
Turn on then off Operating condition setting request (Y9).
Digital conversion is performed in the set sampling cycle regardless of the number of conversion enabled channels.
Item
Setting
• 10ms/8CH (0)
• 20ms/8CH (1)
• 50ms/8CH (2)
• 100ms/8CH (3)
CHAPTER 4 FUNCTIONS
35