4.14

Default Setting Registration Function

Values in the buffer memory can be changed back to the default.
(1) Condition
Use the default setting registration function in a condition where no digital conversion is performed; set Disable
(1) to Conversion enable/disable setting (Un\G0) for all channels.
Check that digital conversion is disabled by confirming Converting or unused (0) is stored in Conversion
completed flag (Un\G10).
If the default setting registration function is used when digital conversion is in process in even one channel, the
error code (116) is stored in Latest error code (Un\G19), and Error flag (XF) turns on. In this case, the values in
the buffer memory do not change back to the default.
(2) Corresponding buffer memory data and default values
Buffer memory areas that correspond to this function are marked with
(
Page 89, Section 6.1); the corresponding data are the same as those for the set value backup function.
Also, the default values are listed in the same table.
(3) How to use
1.
Set Disable (1) to Conversion enable/disable setting (Un\G0) for all channels.
2.
Turn on then off Operating condition setting request (Y9).
3.
Turn on then off Default setting request (Y5). (This operation reads default values to the buffer
memory.)
4.
Change values in the buffer memory if necessary.
5.
Activate the set data by turning on then off Operating condition setting request (Y9).
For details on Default setting request (Y5), refer to the following.
• Output signal (
Page 87, Section 5.2.2)
CHAPTER 4 FUNCTIONS
in the list of buffer memory addresses
4
71