Mitsubishi Electric MELSEC-Q series User Manual page 51

Programmable controller current transformer input module
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

(4) Example settings of the scaling
1: Setting values as: Scaling upper limit value
Ex.
• Input range: 0 to 100AAC
• CH Scaling upper limit value (Un\G63, Un\G65, Un\G67, Un\G69, Un\G71, Un\G73, Un\G75, Un\G77):
20000
• CH Scaling lower limit value (Un\G62, Un\G64, Un\G66, Un\G68, Un\G70, Un\G72, Un\G74, Un\G76): 0
The digital output values and scaling values are as follows:
Scaling upper
limit value
Scaling lower limit value
CT input value (A)
0
25
50
75
100
Scaling lower limit value
>
20000
10000
Scaling value
0
0
CT input value (A)
Digital output value
0
2500
5000
7500
10000
CHAPTER 4 FUNCTIONS
Digital output value
100
Scaling values
0
5000
10000
15000
20000
4
49