Mitsubishi Electric MELSEC-Q series User Manual page 128

Programmable controller current transformer input module
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

(36)CH Logging data setting (Un\G1024 to Un\G1031)
Set whether the logging target is the digital output value or the scaling value for each channel.
For details on the logging function, refer to the following.
• Logging Function (
• In the channel where a setting value other than the above is set, an error occurs. The error code (203) is
stored in Latest error code (Un\G19) and Error flag (XF) turns on. Also, logging cannot be performed.
• When Disable (1) is set to CH Logging enable/disable setting (Un\G1000 to Un\G1007), the setting for
CH Logging data setting (Un\G1024 to Un\G1031) is ignored.
(a) Enabling the setting
Turn on then off Operating condition setting request (Y9) to enable the setting.
(b) Default value
All channels are set to Scaling value (1).
(37)CH Logging cycle setting value (Un\G1032 to Un\G1039), CH Logging cycle
unit setting (Un\G1040 to Un\G1047)
Set the cycle of storing the logging data for each channel.
Set a value for one cycle in CH Logging cycle setting value (Un\G1032 to Un\G1039).
Set a unit of one cycle in CH Logging cycle unit setting (Un\G1040 to Un\G1047).
For details on the logging function, refer to the following.
• Logging Function (
(a) Setting range
• The setting range of CH Logging cycle setting value (Un\G1032 to Un\G1039) depends on the setting for
CH Logging cycle unit setting (Un\G1040 to Un\G1047).
Logging cycle
unit
Update cycle
ms
s
• If a setting above is outside the setting range, an error occurs. The error code (201) is stored in Latest
error code (Un\G19) and Error flag (XF) turns on. Also, logging cannot be performed.
• If the set logging cycle is shorter than the update cycle of the data to be logged, an error occurs. The error
code (202) is stored in Latest error code (Un\G19) and Error flag (XF) turns on. Also, logging cannot be
performed.
• When Disable (1) is set to CH Logging enable/disable setting (Un\G1000 to Un\G1007), the setting
value is ignored.
126
Page 58, Section 4.12)
Logging target
Digital output value
Scaling value
Page 58, Section 4.12)
Setting value of CH Logging cycle
unit setting (Un\G1040 to Un\G1047)
0
1
2
Setting value
0
1
Setting range of CH Logging cycle
setting value (Un\G1032 to Un\G1039)
The setting is ignored.
10 to 32767
1 to 3600