10.2
Conditions for Online Module Change
To perform an online module change, satisfy the following conditions.
Remark
The function version of the first released CT input module is C, and the CT input module supports the online module change.
(1) CPU module
A Process CPU or Redundant CPU is required.
For the precautions on the multiple CPU system configuration, refer to the following.
•
QCPU User's Manual (Multiple CPU System)
For the precautions on the redundant system configuration, refer to the following.
•
QnPRHCPU User's Manual (Redundant System)
(2) Function version of MELSECNET/H remote I/O module
A module of function version D or later is necessary.
(3) Compatible version of programming tools
Programming tool
GX Works2
GX Developer
(4) Restrictions of base unit
When the module is mounted on any of the following base units, an online module change cannot be performed.
• Slim type main base unit (Q3SB)
• Extension base unit (Q5B) which does not require the power supply module (An online module change
cannot be performed for all modules on the base unit.)
System configuration
Normal system
Remote I/O station
Normal system
Remote I/O station
CHAPTER 10 ONLINE MODULE CHANGE
Software version
Version 1.87R or later
Version 1.40S or later
Version 7.10L or later
Version 8.17T or later
10
181