(14)Scaling enable/disable setting (Un\G53)
Set whether the scaling is enabled or disabled for each channel.
For details on scaling function, refer to the following.
• Scaling Function (
When Scaling enable/disable setting (Un\G53) is disabled, 0 is stored in CH Scaling value (Un\G54 to Un\G61).
(a) Enabling the setting
Turn on then off Operating condition setting request (Y9) to enable the setting.
(b) Default value
All channels are set to Disable (1).
(15)CH Scaling value (Un\G54 to Un\G61)
The digital output values after scale conversion by the scaling function are stored for each channel.
The scaling values are stored with 16-bit signed binary.
112
Page 48, Section 4.9)
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5
0
0
0
0
0
0
b8 to b15 are fixed to "0".
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5
Sign bit
1: Negative
0: Positive
b4
b3
0
0
CH8 CH7 CH6 CH5
CH4
b4
b3
Data section
b2
b1
b0
CH3
CH2
CH1
0: Enable
1: Disable
b2
b1
b0