(21)Mode switching setting (Un\G158, Un\G159)
Set the value for the mode to be switched to.
Normal mode
Offset/gain setting mode
When a value out of the setting range above is written, the mode is not switched and only the operating condition is
changed.
(a) Mode switching
To perform the mode switching, turn off then on Operating condition setting request (Y9).
(b) After the mode is switched
When the mode is switched, these areas are cleared and Operating condition setting completed flag (X9) turns
off.
After checking that Operating condition setting completed flag (X9) is off, turn off Operating condition setting
request (Y9).
(c) Default value
The default value is set to 0.
(22)Dropout detection setting (Un\G160)
Set whether to enable or disable the dropout detection for each channel.
For details on the dropout function, refer to the following.
• Dropout Function (
(a) Enabling the setting
Turn on then off Operating condition setting request (Y9) to enable the setting.
(b) Default value
All channels are set to Disable (1).
118
Mode
Page 47, Section 4.8)
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5
0
0
0
0
0
0
b8 to b15 are fixed to "0".
Setting value
Un\G158
0964
H
4144
H
b4
b3
0
0
CH8 CH7 CH6 CH5
CH4
Un\G159
4144
H
0964
H
b2
b1
b0
CH3
CH2
CH1
0: Enable
1: Disable