(16)CH1 Scaling lower limit value (Un\G62) to CH8 Scaling upper limit value
(Un\G77)
Set the range of scale conversion for each channel.
For details on scaling function, refer to the following.
• Scaling Function (
(a) Setting range
• Setting range: -32000 to 32000
• In the channel where a value other than the above is set, an error occurs. The error code (90) is stored
in Latest error code (Un\G19) and Error flag (XF) turns on. The scaling upper limit value and scaling lower
limit value in the channel for which an error occurred operate in the setting before the error occurs.
• When Disable (1) is set to Scaling enable/disable setting (Un\G53), the setting for CH1 Scaling lower limit
value (Un\G62) to CH8 Scaling upper limit value (Un\G77) is ignored.
• Setting the scaling lower limit value more than the scaling upper limit value allows scale conversion with a
negative slope.
(b) Enabling the setting
Turn on then off Operating condition setting request (Y9) to enable the setting.
(c) Default value
All channels are set to 0.
Since 0 is set as the default value, change the set value to use the scaling function.
Page 48, Section 4.9)