Appendix 1.1
G.OFFGAN
GP.OFFGAN
Internal device
Setting
data
Bit
Word
S
(1) Setting data
Device
Un
Start I/O number of the module
Mode change
0: changed to the normal mode
1: changed to the offset/gain setting mode
S
When a value other than above is set, the mode is changed to the offset/gain setting
mode.
(2) Functions
This instruction switches the operation mode of the CT input module.
• Normal mode  offset/gain setting mode (Offset/gain setting mode flag (XA) is on)
• Offset/gain setting mode  normal mode (Offset/gain setting mode flag (XA) is off)
● When the mode is switched from the offset/gain setting mode to the normal mode, Module READY (X0) turns on.
Note that if a sequence program includes the initial settings to be executed at ON of Module READY (X0), this instruction
performs the initial setting process.
● When the mode is switched, the digital conversion stops. To resume the digital conversion, turn on then off Operating
condition setting request (Y9) after switching the mode to the normal mode.
(3) Errors
The instruction has no errors.
234
G(P).OFFGAN
Command
Command
J\
R, ZR
Bit
Word
Description
G.OFFGAN
GP.OFFGAN
U\G
Zn
Setting range
0 to FE
S
Un
S
Un
Constant
Others
$
K, H,
Data type
BIN 16 bits
H
0, 1
BIN 16 bits