2.2.4
Motorized potentiometer
Description
This function is used to simulate an electromechanical potentiometer for setpoint
input.
You can switch between manual and automatic mode for setpoint input. The speci-
fied setpoint is routed to an internal ramp-function generator.
The output of the ramp-function generator for the motorized potentiometer is avail-
able for further interconnection via a connector output (e.g. interconnection to con-
nector input p1070 – CI: main setpoint).
Properties for manual mode (p1041 = "0")
S Separate binector inputs for Raise and Lower are used to adjust the input
setpoint:
– p1035 BI: Motorized potentiometer, setpoint, raise
– p1036 BI: Motorized potentiometer, lower setpoint
S Invert setpoint (p1039)
S Configurable ramp-function generator, e.g.:
– Ramp-up/ramp-down time (p1047/p1048) referred to p1082
– Setting value (p1043/p1044)
– Initial rounding-off active/not active (p1030.2)
S Non-volatile storage via p1030.3
S Configurable setpoint for Power On (p1030.0)
– Starting value is the value in p1040 (p1030.0 = 0)
– Starting value is the stored value (p1030.0 = 1)
Properties for automatic mode (p1041 = "1")
S The input setpoint is specified via a connector input (p1042).
S The motorized potentiometer acts like a "normal" ramp-function generator.
S Configurable ramp-function generator, e.g.:
– Switch on/off (p1030.1)
– Ramp-up/ramp-down time (p1047/p1048)
– Setting value (p1043/p1044)
– Initial rounding-off active/not active (p1030.2)
S Non-volatile storage of the setpoints via p1030.3
S Configurable setpoint for Power On (p1030.0)
– Starting value is the value in p1040 (p1030.0 = 0)
– Starting value is the stored value (p1030.0 = 1)
© Siemens AG 2006 All Rights Reserved
SINAMICS S120 Function Manual, 03/2006 Edition
Extended Setpoint Channel
Extended setpoint channel
2-51