Extended Functions
"Technology controller" function module
Table 4-1
Key parameters for dancer control
Parameter
p1055
n_setp1 downstream of RFG
p2200
BI: Technology controller enable
p2253
CI: Technology controller setpoint 1
p2263
Technology controller type
p2264
CI: Technology controller actual value
(X
)
ACTUAL
p2280
Technology controller p-gain
p2285
Technology controller integral action
time
4.1.5

Commissioning using STARTER

The function module "technology controller" can be activated via the commissio-
ning Wizard or the drive configuration (configure DDS).
You can check the actual configuration in parameter r0108.16.
4-182
Designation
Example
p1055 = r2294 Tec_ctrl output_sig [FP 3080]
p2200 = 1 Technology controller enabled
p2253 = r2224 Fixed setpoint active [FP 7950]
p2263 = 1 D component in fault signal [FP 7958]
p2264 = r4055 [1] Analog input AI1 of TB30
p2280 Determine by optimization
p2285 Determine by optimization
© Siemens AG 2006 All Rights Reserved
SINAMICS S120 Function Manual, 03/2006 Edition