Extended Functions

Switching-in a drive object x_Infeed using a vector drive object

4.20
Switching-in a drive object x_Infeed using a vector drive
object
Description
BI: Acknowledge fault
p2105[C]
BI: AR connection
p1207
BI: ON/OFF1
p0840 [C]
Fig. 4-16
Using this BICO interconnection, a drive object (DO) x_Infeed can be switched-in
by a vector drive object. This power-on version is mainly used for chassis units, if
only a line module and one Motor Module are used. If the associated application
requires an automatic restart function then the following procedure is recommen-
ded in order to implement it:
S The automatic restart function is activated on the DO vector (p1210).
S In addition to the automatic restart function, the flying restart function (p1200)
must be activated on DO vector if it must be assumed that an automatic restart
must be made for a motor that is still rotating.
Individual steps when restarting:
S After the line supply returns and the electronics has booted, the faults that have
occurred at DO vector as a result of its automatic restart are acknowledged
depending on the settings in p1210.
S The faults of the DO x_Infeed are acknowledged via the connection r1214.4 =>
p2105.
S The ON command (p0840) for the infeed is generated via the binector output
"control line contactor" of the DO vector (p0863.1).
S The power-on attempt is interrupted if, during the new power-on sequence, a
fault occurs on the DO x_Infeed. The fault is communicated to the DO vector
via the BiCo connection p1208.0 => r2139.3 shown above.
S The automatic restart of the DOs x_Infeed have absolutely no significance for
the described power-on version.
4-230
DO x _Infeed
Infeed operation
r0863 .0
Infeed fault
(1214 .4)
r2139 .3
Infeed power failure
(1214 .2)
r0863 .2
Close line contactor
(0863.1)
r0863 .1
Line
contactor
BICO interconnection
DO vector
Infeed oper.
p0864
BI: Infeed fault
AR status
p1208 .0
(2139 .3)
AR active
BI: Infeed power failure
p1208 .1
Close line contactor
(0863 .2)
r0863 .1
© Siemens AG 2006 All Rights Reserved
SINAMICS S120 Function Manual, 03/2006 Edition
r1214 .4
r1214 .2