Infeed
Basic Infeed
Switching on the Basic Line Module:
Fig. 1-8
Note
Under the condition that the drive system was commissioned with STARTER and
no PROFIBUS telegram was activated, the infeed can be powered-up by issuing
an enable signal at the EP terminals and a positive signal edge at OFF1 (p0840).
Switching off the Basic Line Module
To switch off the Active Line Module, carry out the steps for switching it on in re-
verse order.
Switching off the controller with the OFF1 signal is delayed by the time entered in
p3490, thereby allowing the connected drives to be decelerated in a controlled
manner.
1-36
POWER ON
S1: Power-on disable
<2>
ZSWAE.0/1/2 = 0
"Commissioning complete"
(p10 = 0 and p9 = 0)
"0 = OFF1" (STWAE.0)
<2>
"0 = OFF2" (STWAE.1)
S2: Ready to power up
<2>
ZSWAE.1/2/6 = 0
<3>
Line contactor is de-energized
Wait for power on
"0 = OFF1"
(STWAE.0)
<2>
p0862
ON
delay
S3a: Line contactor
switch-in
S4: Operation
ZSWAE.0/1/2 = 1
<2>
Pulses and controllers enabled
Vdc powered up via ramp
Basic Infeed ramp-up
ZSWAE.6 = 1
3x
<3>
&
22
ZSWAE.0 = 1
<3>
&
T
21
<3>
<1> POWER ON = 24 V electronics
Pre–charging
<2> STWAE.xx = control word
00
<3>
ZSWAE.6 = 0
<3> r0002 = operating display
© Siemens AG 2006 All Rights Reserved
SINAMICS S120 Function Manual, 03/2006 Edition
supply OFF ––> ON
or RESET button.
PROFIBUS supply bit xx,
ZSWAE.xx = status word
PROFIBUS supply bit xx