Logging Menu - ABB ScreenMaster RVG200 Operating Instructions Manual

Paperless recorder
Hide thumbs Also See for ScreenMaster RVG200:
Table of Contents

Advertisement

ScreenMaster RVG200
Paperless recorder

5.2 Logging menu

Logging
Online
Select Line Status
Archive all Historical Data
External Media Inserted.
Press Enter to 'Go Online'
Press Cancel to 'Stay Offline'.
If no action taken, Archiving
will Go Online in 8 secs.
Offline
52
Touch to display the Operator menu.
Touch to display the sub-menu.
Note. Greyed-out if no archive media is inserted
None (see Section 7.7.2, page 70)
historical review mode (see page 40).
Logging is off-line. Touch to set logging on-line and start the archiving
process.
When external archive media is inserted, a dialog is displayed giving the User
the option of setting logging on-line and starting the archiving process or
remaining off-line. If no action is taken within 10 seconds, logging is set
on-line and archiving is started automatically.
If the Archive all Historical Data checkbox is de-selected, older unarchived
data remains in the internal memory buffer until overwritten by newer data but
is not available for archiving unless 'Reset archiving' (see page 53) is
selected.
Note. Greyed-out if the recorder has been placed in historical review mode.
Logging is on-line. Touch to set logging off-line and stop the archiving
process.
Recording of channel data into internal memory continues uninterrupted but
archiving to the selected storage media is suspended until logging is set
on-line again.
Note.
Always set logging off-line before changing the storage media type
selection (see Section 7.7.2, page 70) or removing external media. A
warning is displayed if the storage media type selection is changed or
external media is removed before logging is set off-line.
When logging is set off-line, an Updating archiving progress bar is
displayed. Do not remove external media until archiving is complete.
To stop archiving, touch Stop Immediately.
Archive Media is set to
or
the recorder has been placed in
or
5 Logging
OI/RVG200-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents