E.3.3 Batch configuration
To configure batch recording, access Process Group Configuration (see Section 7.8, page 80), select the
required Process Group and select the Batch tab. Exit and save the configuration when complete.
Batch
Enable Batch Recording
Enable Batch Recording
Note. The following parameters are displayed only if
Batch Type
Start/Stop, Abort
Start/Stop Batch Source
Batch Power Failure
Operator Login
178
Set to On to enable batch recording for the selected process group.
Touch
to toggle between Standard and Concurrent.
Select a digital signal source to start batch recording on a rising edge and
stop batch recording on a falling edge.
Note. If Batch Number (see next page) is set to Off or Text and a batch is
started using a digital signal, the contents of the Batch Number and
batch identification fields (if configured – see next page) are copied
automatically to the new batch. If Batch Number is set to Automatic, the
content of the Batch Number field is incremented by one, automatically.
Select a time between 1 minute and 2 hours to enable this function or
select Off to disable it.
If this function is enabled and electrical power is lost for more than the
time selected, the batch is stopped and a digital
is activated for 5 seconds.
Note. The value selected affects all groups. The default value is Off.
Select the type of batch recording security required:
Start
the operator is required to enter a password to start
batch recording.
Start and
the operator is required to enter a password to start
Stop
and stop batch recording.
Disabled
batch recording security is disabled.
Note.
Batch recording security can be enabled only if
set to Advanced (see Section E.3.1, page 177), If
set to Basic this parameter is set automatically to Disabled and the
edit button is not displayed.
If this parameter is set to Disabled no security is required to start or
stop batch recording and the operator name is not displayed.
Appendix E – Batch recording
Enable Batch Recording
is set to On.
signal
Batch Power Failure
Security system
Security system