Page 4
Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
(EMC Directive 2014/30/EU) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2014/35/EU). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
Section 1 1MRS757261 E Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the device. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering the communication setup in a...
Section 1 1MRS757261 E Introduction Product documentation 1.3.1 Product documentation set Quick start guide Quick installation guide Brochure Product guide Operation manual Installation manual Engineering manual Technical manual Application Engineering guide Communication protocol manual Point list manual Commissioning manual GUID-6347995B-5555-49B2-BE69-ACF6EBA213DA V1 EN Figure 1: The intended use of documents during the product life cycle See the 630 series documentation for installation and commissioning...
IEC 61850 Communication Protocol Manual 1MRS757260 Operation Manual 1MRS757183 Technical Manual 1MRS757256 Download the latest documents from the ABB Web site http://www.abb.com/relion. Symbols and conventions 1.4.1 Symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
Section 1 1MRS757261 E Introduction • Abbreviations and acronyms are spelled out in the glossary. The glossary also contains definitions of important terms. • Push button navigation in the LHMI menu structure is presented by using the push button icons. To navigate between the options, use •...
Page 13
Section 1 1MRS757261 E Introduction Functionality IEC 61850 Information exchange between peer PML630s PPLSGGIO Disturbance recorder functions Analog channels 1-10 (samples) A1RADR Analog channel 11-20 (samples) A2RADR Analog channel 21-30 (samples) A3RADR Analog channel 31-40 (calc. val.) A4RADR Binary channel 1-16 B1RBDR Binary channel 17-32 B2RBDR...
Section 3 1MRS757261 E Logical node extensions 3.1.3 LSCCCLS Table 6: LSCCCLS Attribute name DATA type Explanation M/O/E CCLS class Contingency load shedding (manual CCLS Data Common logical node information Mode (manual load shed function ABB_c_dINC Enable / Disable / Test command/ status) Behaviour (reflects the mode of the ABB_a_dINS...
Section 3 1MRS757261 E Logical node extensions Attribute name DATA type Explanation M/O/E Total amount of sheddable load in NtwShdLod ABB_c_dMV subnetwork NtwALodShd ABB_c_dMV Actual load shed NtwTotLoad ABB_c_dMV Total load in the sub network NtwMustLS ABB_c_dMV Must be load shed NtwPwrImb ABB_c_dMV Power imbalance in the subnetwork...
Section 3 1MRS757261 E Logical node extensions Attribute name DATA type Explanation M/O/E ALodPrio5 ABB_c_dMV Accumulated load against priority 5 ALodPrio6 ABB_c_dMV Accumulated load against priority 6 ALodPrio7 ABB_c_dMV Accumulated load against priority 7 ALodPrio8 ABB_c_dMV Accumulated load against priority 8 ALodPrio9 ABB_c_dMV Accumulated load against priority 9...
Page 22
Section 3 1MRS757261 E Logical node extensions Attribute name DATA type Explanation M/O/E NtwNumSrc1 ABB_b_dINS Subnetwork number of power source1 NtwNumSrc2 ABB_b_dINS Subnetwork number of power source2 NtwNumSrc3 ABB_b_dINS Subnetwork number of power source3 NtwNumSrc4 ABB_b_dINS Subnetwork number of power source4 NtwNumSrc5 ABB_b_dINS Subnetwork number of power source5...
Section 3 1MRS757261 E Logical node extensions Extended logical nodes Table 10: Logical nodes included in the IED LN Class Prefix LN Type Description (default) LLN0 LLN0 General LN0 for LD0 LN0 for load busbar (load circuit breaker and power) LDLLN0 information LSLLN0...
Section 3 1MRS757261 E Logical node extensions 3.2.1 LLN0 Table 11: LLN0 Attribute name DATA type Explanation M/O/E LLN0 General LN0 for LD0 Data Common Logical Node Information ABB_c_dINC Mode ABB_a_dINS Behaviour Health ABB_c_dINS Health NamPlt ABB_b_dLPL Name plate 3.2.2 LDLLN0 Table 12: LDLLN0...
Section 3 1MRS757261 E Logical node extensions 3.2.4 SNWLLN0 Table 14: SNWLLN0 Attribute name DATA type Explanation M/O/E LLN0 LN0 for SubNetwork information Data Common Logical Node Information ABB_c_dINC Mode ABB_a_dINS Behaviour Health ABB_c_dINS Health NamPlt ABB_b_dLPL Name plate 3.2.5 NCBDLLN0 Table 15: NCBDLLN0...
Section 3 1MRS757261 E Logical node extensions 3.2.7 PSLLN0 Table 17: PSLLN0 Attribute name DATA type Explanation M/O/E LLN0 class LN0 for power source function LLN0 (Generator/Grid/Utility transformer) information Data Common logical node information ABB_a_dINC Mode ABB_a_dINS Behaviour Health ABB_c_dINS Health NamPlt ABB_ln0_dLPL...
Section 3 1MRS757261 E Logical node extensions Attribute name DATA type Explanation M/O/E NamPlt ABB_ln0_dLPL Name plate Status information ABB_d_dACD Any load shed function start ABB_b_dACT Any load shed function operate 3.2.10 LSPTRC Table 20: LSPTRC Attribute DATA type Explanation M/O/E PTRC class PTRC...
Section 3 1MRS757261 E Logical node extensions 3.2.12 PSMMXU Table 22: PSMMXU Attribute name DATA type Explanation M/O/E MMXU class Power source (Generator/Grid/Utility MMXU transformer) information Data Common logical node information ABB_a_dINC Mode ABB_a_dINS Behaviour Health ABB_c_dINS Health NamPlt ABB_a_dLPL Name plate Measurement information TotW...
Section 3 1MRS757261 E Logical node extensions Attribute name DATA type Explanation M/O/E Health ABB_c_dINS Health NamPlt ABB_b_dLPL Name plate Control ABB_v1_dSPC Demand reset operation Measurements WhDmd ABB_v2_dMV Real energy demand Status information ABB_v1_dSPS Maximum demand operate alarm Time interval in seconds for demand TmmDmdPer ABB_v1_dINS calculation...
Section 3 1MRS757261 E Logical node extensions 3.2.15 NPMMXU Table 25: NPMMXU Attribute name DATA type Explanation M/O/E MMXU class MMXU Network power source power value Data Common logical node information ABB_c_dINC Mode ABB_a_dINS Behaviour Health ABB_c_dINS Health NamPlt ABB_b_dLPL Name plate Measurements AvaPwrSrc1...
Section 3 1MRS757261 E Logical node extensions 3.2.17 NCBDMMXU Table 27: NCBDMMXU Attribute DATA type Explanation M/O/E MMXU class Network circuit breaker power flow MMXU value Data Common logical node information ABB_c_dINC Mode ABB_a_dINS Behaviour Health ABB_c_dINS Health NamPlt ABB_b_dLPL Name plate Measurement TotW...
Section 3 1MRS757261 E Logical node extensions Attribute name DATA type Explanation M/O/E ABB_a_dINS Behaviour Health ABB_c_dINS Health NamPlt ABB_b_dLPL Name plate Measurements TotW ABB_c_dMV Active power Status information InhLSSt ABB_v1_dINS Load shed inhibit status for load feeder LodPrioSt ABB_v1_dINS Feeder priority 3.2.20 PPLSGGIO...
Section 3 1MRS757261 E Logical node extensions 3.2.21 SPGGIO Table 31: SPGGIO Attribute name DATA type Explanation M/O/E GGIO Class GGIO Test mode status of PML630 IED Data Common logical node information ABB_a_dINC Mode ABB_a_dINS Behaviour Health ABB_c_dINS Health NamPlt ABB_a_dLPL Name plate Status information...
Section 3 1MRS757261 E Logical node extensions 3.2.23 DPGGIO Table 33: DPGGIO Attribute DATA type Explanation M/O/E GGIO class GGIO Generic Double Point status Data Common logical node information ABB_a_dINC Mode ABB_a_dINS Behaviour Health ABB_c_dINS Health NamPlt ABB_a_dLPL Name plate Status DPCSO ABB_b_dDPC...
Section 3 1MRS757261 E Logical node extensions Attribute name DATA type Explanation M/O/E Remarks Common Logical Node Information ABB_a_dINC Mode ABB_a_dINS Behaviour Health ABB_c_dINS Health NamPlt ABB_a_dLPL Name plate Status Information RsCnt ABB_v1_dSPC Reset counters Controllable Cnt1 ABB_v1_dBCR Output of counter 1 Data type for counter value is INT32...
Section 3 1MRS757261 E Logical node extensions Attribute DATA type Explanation M/O/E Health ABB_c_dINS Health NamPlt ABB_a_dLPL Name plate Status AnIN ABB_a_dMV Measurement Value 3.2.27 SPVNZBAT Table 37: SPVNZBAT Attribute DATA type Explanation M/O/E ZBAT class ZBAT Station battery supervision Data Common logical node information ABB_a_dINC...
Section 4 1MRS757261 E Glossary Section 4 Glossary Behavior cPMS Compact power management solution Data extension to IEC 61850-7-4 Electromagnetic compatibility International Electrotechnical Commission IEC 61850 International standard for substation communication and modeling Intelligent electronic device Logical device zero (0) LHMI Local human-machine interface LLN0...