ABB ScreenMaster RVG200 Operating Instructions Manual page 144

Paperless recorder
Hide thumbs Also See for ScreenMaster RVG200:
Table of Contents

Advertisement

ScreenMaster RVG200
Paperless recorder
Inputs
Linear inputs
Millivolts
Milliamps
Volts
Resistance  (low)
Resistance  (high)
Sample interval
Channel-to-channel input isolation
Isolation from rest of recorder
The figures in the following table include linearizer and electrical errors
Thermocouple
B
C
D
E
J
K
L
N
R
S
T
RTD
PT100
PT1000 (IEC 60 751)
Ni120
Ni1000
142
Standard analog input
–150 to 150 mV
–50 to 50 mA
–10 to 24 V*
0 to 550 
0 to 10000 
125 ms per sample
(all inputs are processed in parallel)
Galvanically isolated to 500 V DC
Galvanically isolated to 500 V DC
Maximum range
ºC
250 to 1800
482 to 3272
0 to 2300
32 to 4172
0 to 2310
32 to 4190
–100 to 900
–148 to 1652
–100 to 900
–148 to 1652
–100 to 1300
–148 to 2372
–100 to 900
–148 to 1652
–200 to 1300
–328 to 2372
–50 to 1700
–58 to 3092
–50 to 1700
–58 to 3092
–200 to 300
–328 to 572
–200 to 600
–328 to 1112
–200 to 850
–328 to 1562
–80 to 260
–112 to 500
–30 to 130
–22 to 266
Accuracy
(% of reading)
0.1 % or ±20 µV
0.1 % or ±10 µA
0.1 % or ±10 mV
0.1 % or ±0.5 
0.1 % or ±5 
ºF
0.1 % or ±0.3 ºC (0.54 ºF) (above 300 ºC [572 ºF])
0.1 % or ±0.3 ºC (0.54 ºF) (above 200 ºC [392 ºF])
8 Specification
Measurement accuracy
(% of reading)
0.1 % or ±1 ºC (1.8 ºF)
0.1 % or ±0.5 ºC (0.9 ºF)
0.1 % or ±1.5 ºC (2.7 ºF)
0.1 % or ±0.3 ºC (0.54 ºF)
0.1 % or ±0.3 ºC (0.54 ºF)
0.1 % or ±0.3 ºC (0.54 ºF)
0.1 % or ±0.3 ºC (0.54 ºF)
0.1 % or ±0.3 ºC (0.54 ºF)
0.1 % or ±0.3 ºC (0.54 ºF)
0.1 % or ±0.5 ºC (0.9 ºF)
0.1 % or ±0.5 ºC (0.9 ºF)
0.1 % or ±0.5 ºC (0.9 ºF)
0.1 % or ±0.5 ºC (0.9 ºF)
OI/RVG200-EN