Unit Communication Card Verification; Table 2-5. Tpu2000R Communication Card Matrix - ABB TPU2000 Technical Manual

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

"Z"
"Q"
COM 1
Digit
Digit
RS232
NOTE 1- Available if Digit "Y" is 0 or 5.Front Panel Interface not included. Unavailable if Digit "Y" is 1 or 6.
The visual identification of a TPU2000R communication card is completed through visual inspection of the card
component location and the part number of the base printed circuit board as illustrated in Table 2-5.

Table 2-5. TPU2000R Communication Card Matrix

"Z" Digit
Raw Circuit Board Part Number
1
COMM 485 PCB
613709-005 REV0
2
2000R AUX COM
613708-005 REV0
3
613708-005 REV0
4
613708-005 REV0
5
COMM 485 PCB
613709-005 REV0
6
MODBUS COMM PCB
613720-002 REV1
7
MODBUS COMM PCB
613720-002 REV1
8
AUX & AUX
613755-002 REV0
E
613850

Unit Communication Card Verification

There are several ways to identify the communication cards inserted in the TPU2000 or TPU2000R units. Some
of the methods require the unit to be powered up. Other methods require the unit to be taken out of service.
To identify the unit part number of the present TPU2000 or TPU2000R, the following steps may be executed to
facilitate unit identification.
1. With the unit energized, if the unit has a Front Panel LCD (Refer to Tables 2-1 through 2-4 inclusive for
identification) Interface:
1. Depress the "E" Key.
2. Depress the Arrow Down Key "↓" once to highlight the SETTINGS field. Depress the "E"
3. Depress the Arrow Down Key "↓" twice to highlight the UNIT INFORMATION field.
4. The Serial Number and Catalog Number shall be displayed.
If the Unit does not have a Front Panel LCD Interface (Refer to Tables 2-1 through 2-4 inclusive for identification)
and the user has WinECP or if the user wishes not to use the unit's Front Panel Interface:
1. Start WinECP.
2. Depress the "DIRECT ACCESS" selection button presented in the pop-up window.
3. Depress the "CONNECT" option selection presented within the pop-up window.
4. Select the "HELP" Menu option at the top right-hand section of the menu bar.
5. Select the Drag-Down Menu item "UNIT INFORMATION".
6. A pop-up window shall appear with the Serial Number and Catalog Number.
TPU2000/2000R Modbus/Modbus Plus Automation Guide
COM 2
RS232
AUX COM
AUX COM
Key.
Depress the "E" key.
COM 3
Components To Look For
Parts near black 9 pin 232 connector are populated
Parts in middle of board are not populated - 2 DC/DC
Converters (U1 & U8)
Only parts in middle of board - no DC/DC
Converters, has Transformer T2
Parts near black 9 pin 232 connector are not
populated - only 1 DC/DC Converter (U1)
Parts near green connector are populated
RS485 option parts NOT populated (area inside
dotted border)
Fully populated
Fully populated
----------------------------------------------------
AUX COM
INCOM
RS485
or Ethernet Fiber
Optic
Time
Synch
9