1. From the metering screen depress the "E" key.
2. Depress the "↓" key once to select the SETTINGS Menu and then depress the "E" pushbutton.
3. Depress the "↓" key once to select the CHANGE SETTINGS Menu selection. Depress the "E" pushbutton.
4. Depress the "↓" key seven times to select the COMMUNICATIONS Menu and then depress the "E"
pushbutton.
5. Enter the unit's password, one digit at a time. The default password is four spaces. Depress the "E"
pushbutton once.
6. The CHANGE COMMUNICATION SETTINGS Menu shall be displayed. With the cursor at the Unit Address
field, depress "E". The unit address can be modified. The address selected in this field will configure the
address for the entire node. Use the "↓" and "↑" arrow keys to select the password digit entry. Use the "→"
and "←" keys to select the digit to configure. Depress "E" to save the digits. Depress "C" to return to the Root
Menu.
7. Once returned to the Main Menu, depress the "↓" key four times to select the RP RS232 BAUD RATE (SEE
NOTE 1) Menu and then depress the "E" pushbutton. The selections for the menu are listed in Table 4-1.
Use the "→" and "←" keys to select the baud rates for the port. Depress "E" to select the entry. Depress "C"
to return to the Root menu.
8. Once returned to the Main Menu, depress the "↓" key once to select the RP RS232 FRAME
(SEE NOTE 2) Menu and then depress the "E" pushbutton. The selections for the menu are listed in Table 4-
1. Use the "→" and "←" keys to select the baud rates for the port. Depress "E" to select the entry. Depress
"C" to return to the Root Menu.
9. Once returned to the Main Menu, depress the "↓" key once to select the RP RS485 BAUD RATE (SEE NOTE
3) menu and then depress the "E" pushbutton. The selections for the menu are listed in Table 4-1. Use the
"→" and "←" keys to select the baud rates for the port. Depress "E" to select the entry. Depress "C" to return
to the Root Menu.
10. Once returned to the main menu, depress the "↓" key once to select the RP RS485 FRAME (SEE NOTE 4)
menu and then depress the "E" pushbutton. The selections for the menu are listed in Table 4-1. Use the "→"
and "←" keys to select the baud rates for the port. Depress "E" to select the entry. Depress "C" to return to
the Root Menu.
11. Once returned to the Main Menu, depress the "↓" key once to select the RP IRIG B selection. Refer to
Section 5 to determine the configuration for the IRIG B of the unit.
12. Once returned to the Main Menu, depress the "↓" key once to select the PARAMETER 1 Menu and then
depress the "E" pushbutton. The selections for this field may range from 0 to 255. Use the "→" and "←" keys
to select appropriate entry for Parameter 1 as described above. Depress "E" to select the entry. Depress "C"
to return to the Root Menu.
13. Once returned to the Main Menu, depress the "↓" key twelve times to select the MODE PARAMETER 1 Menu
item and then depress the "E" pushbutton. The selections for this field are enable and disable. Use the "→"
and "←" keys to select appropriate entry for MODE PARAMETER 1 as described above. Depress "E" to
select the entry. Depress "C" to return to the Root Menu.
14. Once returned to the Main Menu, depress the "↓" key once to select the MODE PARAMETER 2 Menu item
and then depress the "E" pushbutton. The selections for this field are enable and disable. Use the "→" and
"←" keys to select appropriate entry for MODE PARAMETER 1 as described above. Depress "E" to select
the entry. Depress "C" to return to the Root Menu.
15. To Save the selections configured in the previous steps depress the "C" pushbutton.
presented to the operator "Enter YES to save settings <NO>". Use the "→" and "←" keys to select the option
YES and depress "E" to save the settings.
A query will be