ABB TPU2000 Technical Manual page 209

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

Register
Address
61174
150P-1 Time Dial
61175
46-1 Curve Select Byte
61176
46-1 Pickup Amps
61177
46-1 Time Dial/ Time Delay
61178
51N-1 Curve Select (TYPE II)
61179
51N-1 Pickup Amps
61180
51N-1 Time Dial
61181
50N-1 Curve Select Byte (TYPE II)
61182
51N-1 Pickup Amps
61183
51N-1 Time Dial/Delay Setting
61184
150N-1 Curve Select (TYPE II)
61185
150N-1 Pickup Amps
61186
150N-1 Time Delay
61187
87T-2 Tap Amp Setting
61188
51P-2 Curve Select Byte (TYPE I)
61189
51P-2 Pickup Amp/OA
61190
51P-2 Time Dial/Delay Setting
61191
51P-2 Curve Select (TYPE I )
61192
51P-2 Pickup Amps
61193
51P-2 Time Dial/Time Delay
61194
51P-2 Curve Select (TYPE II)
61195
51P-2 Pickup X Amps
61196
51P-2 Time Dial/Time Delay
TPU2000/2000R Modbus/Modbus Plus Automation Guide
Item
Unsigned 16 Bits
0<=Range<=9.99 * 100
Unsigned Integer 16 bits
See Table Above
Unsigned 16 Bits
1<=Range<= 12 *10
0.2<=Range<=2.4 Amp * 50 (See Note)
Unsigned 16 Bits
1<=Range<=12 * 10
0.2<=Range<= 0.4 *50
Unsigned 16 Bits
Range 0-12 (See Text Above)
Unsigned 16 Bits
1<=Range<= 12 *10
0.2<=Range<=2.4 Amp * 50 (See Note)
Unsigned 16 Bits
1<=Range <=20 /Delay Byte
0<=Range<=10 * 20 51N Time Multiplier
Unsigned Integer 16 bits
0<=Range<=12 (See Text Above)
Unsigned 16 Bits
0.5<=Range<= 20 *10
Unsigned 16 Bits
Time Dial * 10
Delay * 100
Unsigned Integer 16 bits
See Table Above
Unsigned 16 Bits
0.5<=Range<= 20 *10
Unsigned 16 Bits
0<=Range<=9.99 * 100
Unsigned 16 Bits
2<=Range<=9 Amperes * 10
0.4<=Range <=1.8 * 50
Unsigned 16 Bits (See Text Above)
Unsigned 16 Bits
1<=Range<=12 *10
0.2<=Range<=2.4 * 50
Unsigned 16 Bits
Dial : 1<=Range<=10 *20
Delay : 0<=Range<=10 * 20
Unsigned 16 Bits
Range 0-12 (See Text Above)
Unsigned 16 Bits
1<=Range<= 12 *10
0.2<=Range<=2.4 Amp * 50 (See Note)
Unsigned 16 Bits
1<=Range <=10 (X20) Time Dial
0<=Range<=10 (X20) Time Delay
Unsigned 16 Bits
Range 0-12 (See Text Above)
Unsigned 16 Bits
0.5<=Range<=20 Amp * 10 (See Note)
Unsigned 16 Bits
Time Dial * 10
Time Delay * 20
Description
199

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tpu2000r

Table of Contents