ABB TPU2000 Technical Manual page 205

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

Register
Address
61062
51P-2 Time Dial /Delay Setting
61063
51P-2 Curve Select (TYPE I )
61064
51P-2 Pickup Amps
61065
51P-2 Time Dial/Time Delay
61066
51P-2 Curve Select (TYPE II)
61067
51P-2 Pickup X Amps
61068
51P-2 Time Dial/Time Delay
61069
46-2 Curve Select (TYPE I)
61070
46-2 Pickup Amps
61071
46-2 Time Dial/ Time Delay
61072
51G-2 Curve Select (TYPE II)
61073
51G-2 Pickup Amps
61074
51G-2 Time Dial/Time Delay
61075
50G-2 Curve Select Byte (TYPE II)
61076
51G-2 Pickup Amps
61077
51G-2 Time Dial/Delay Setting
61078
150G-2 Curve Select (TYPE II)
61079
150G-2 Pickup Amps
61080
150G-2 Time Delay
61081
Disturb 2 Pickup X
61082
Level Detector-1 Pickup X
61083
Level Detector-1 Pickup X
61084
Unit Configuration Byte
TPU2000/2000R Modbus/Modbus Plus Automation Guide
Item
1<=Range<=12 *10
0.2<=Range<=2.4 * 50
Unsigned 16 Bits
Dial : 1<=Range<=10 *20
Delay : 0<=Range<=10 * 20
Unsigned 16 Bits
Range 0-12 (See Text Above)
Unsigned 16 Bits
1<=Range<= 12 *10
0.2<=Range<=2.4 Amp * 50 (See Note)
Unsigned 16 Bits
1<=Range <=10 (X20) Time Dial
0<=Range<=10 (X20) Time Delay
Unsigned 16 Bits
Range 0-12 ( See Text Above)
Unsigned 16 Bits
0.5<=Range<=20 Amp * 10 (See Note)
Unsigned 16 Bits
Time Dial * 10
Time Delay * 20
Unsigned Integer 16 bits
See Table Above
Unsigned 16 Bits
1<=Range<= 12 *10
0.2<=Range<=2.4 Amp * 50 (See Note)
Unsigned 16 Bits
1<=Range<=10 * 20
0<=Range<= 10 *20
Unsigned 16 Bits
Range 0-12 (See Text Above)
Unsigned 16 Bits
1<=Range<= 12 *10
0.2<=Range<=2.4 Amp * 50 (See Note)
Unsigned 16 Bits
1<=Range <=10 * 20 : Time Dial
0<=Range<=10 * 20 : Time Delay
Unsigned Integer 16 bits
0<=Range<=12 (See Text Above)
Unsigned 16 Bits
0.5<=Range<= 20 *10
Unsigned 16 Bits
Time Dial * 10
Delay * 100
Unsigned Integer 16 bits
See Table Above
Unsigned 16 Bits
0.5<=Range<= 20 *10
Unsigned 16 Bits
0<=Range<=9.99 * 100
Unsigned Integer 16 Bits
0.5<= Range<=5 *10
Unsigned Integer 16 Bits
0.5<= Range<=20 *10 , 201 = Disable
Unsigned Integer 16 Bits
0.5<= Range<=20 *10 , 201 = Disable
Unsigned Integer 16 Bits (rightmost bit)
Description
195

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tpu2000r

Table of Contents