Table 5-36. 3 Winding Through Fault Record Buffer Modbus Register Definition - ABB TPU2000 Technical Manual

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
Register
Address
41834
I 0-2 (Ang) – Zero Sequence
Angle Winding 2
41835
I 1-2 (Ang) – Positive
Sequence Angle Winding 2
41836
I 2-2 (Ang) – Negative
Sequence Angle Winding 2
41837
Scale - Phase Wdg 1
41838
Scale - Phase Wdg 2
41839
Scale - Neutral Wdg 1
41840
Scale - Neutral Wdg 2
The 3 Winding Through Fault Register Definition Table follows.

Table 5-36. 3 Winding Through Fault Record Buffer Modbus Register Definition

Register
Address
42433
3 Winding Through Fault
Control Register
1 = First Record
2 = Next Record
3 = Oldest Unreported Record
42434
Parameter Flag
42435
Fault Type Element
42436
Setting At Fault Event
42437
Fault Record Number
42438
Year
42439
Month
42440
Day
Item
Unsigned 16 Bit
Unsigned 16 Bit
Unsigned 16 Bit
Unsigned 16 Bit
Unsigned 16 Bit
Unsigned 16 Bit
Unsigned 16 Bit
Item
Fault Record Control Register
Unsigned 16 Bit
1 = Fill Register 42434 through 42466 with First Record in
Data Buffer.
2 = Fill Register 42434 through 42466 with with next Record
Data pointed to in buffer.
3 = Fill Register 42434 through 42466 with with the last
(oldest unreported) record of data.
Unsigned Integer 16 Bit
Unsigned 16 Bit
00 = 87T – % Differential Alarm
01 = 87H – High Set Inst. Differential Alarm
02 = 51P-1 – Winding 1 Phase Time Overcurrent
03= 51P-2 – Winding 2 Phase Time Overcurrent
04 = 50P-1 – 1
05 = 50N-1 – 1
06 = 150P-1 – 2
07 =150N-1 – 2
08 = 46-1 – Neg. Sequence 1 Inst. Time Overcurrent
09 = 51P-2 – Winding 2 Phase Time Overcurrent
10 = 51G-2 – Winding 2 Ground Time Overcurrent
11 = 50P-2 – 1
12 =50G-2 – 1
13 = 150P-2- 2
14 = 150G-2- 2
15 = 46-2- Neg Sequence 2 Inst. Time Overcurrent
16 = ECI-1 – Event Capture Initiate 1
17 = ECI-2 – Event Capture Initiate 2
18 = Through Fault
19 = Harmonic Restraint
Unsigned 16 Bit
01 = Primary Settings
02 = Alternate 1 Settings
04 = Alternate 2 Settings
Unsigned 16 Bit
(1 – 999, only last 32 kept)
2 digit 00 -99
Unsigned 16 Bit Year of Fault
1 - 12
Unsigned 16 Bit Month of Fault
1 - 31
Unsigned 16 Bit Day of Fault
Description (Multiplier if any)
Description (Multiplier if any)
st
Winding 1 Phase Inst. Overcurrent
st
Winding 1 Neutral Inst. Overcurrent
nd
Winding 1 Phase Inst. Overcurrent
nd
Winding 1 Neutral Inst. Overcurrent
st
Winding 2 Phase Inst. Overcurrent
st
Winding 2 Ground Inst. Overcurrent
nd
Winding 2 Phase Inst.Overcurrent
nd
Winding 2 Ground Inst Overcurrent
124