Table 5-17. Fast Status Modbus Address Map Definition

Register
Address
40170
Fast Status
Bit 0 - 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10 – 15
40171
Fast Status
Bit 0
Division Code (Lsb)
Bit 1
Division Code
Bit 2
Division Code
Bit 3
Division Code
Bit 4
Division Code
Bit 5
Division Code
Bit 6
Unreported Record
Bit 7
Reserved
Bit 8
Heartbeat Timer
Bit 9
Heartbeat Timer
Bit 10
Heartbeat Timer
Bit 11
Heartbeat Timer
Bit 12
Heartbeat Timer
Bit 13
Bit 14
Heartbeat Timer
Bit 15
Heartbeat Timer (Msb)

Communication Event Log (8 Registers Defined)

Whenever a communication error occurs, the TPU2000/TPU2000R generates an exception response to the
rejected command.
Registers 40172 through 40179 contains information on the last communication error
experienced via the front communication port, rear INCOM port or the RS232/485 ports resident on the relay's
communication card. Table 5-18 lists the register definition for the event log.

Table 5-18. Communication Error Event Log

Address
40172
Last Comm Port Error
40173
Last Comm Error
Command
40174
Last Comm Error Register
Request
40175
Last Comm Error Type
Item
Reserved ( Lsb)
Reserved
Reserved
Reserved
Reserved
Product ID (Msb)
Heartbeat Timer
Item
Unsigned Integer
0 = Modbus Plus (Type 6 or 7 Card Only TPU2000R)
1 = INCOM
2 = RS232
3 = RS485
4 = Ethernet
Unsigned Integer/ Word Byte Decode
If Modbus or Modbus Plus, register contains Modbus Command. If
INCOM or Standard Ten Byte, register contains Command +
Subcommand in upper lower byte decode.
Unsigned Integer
Last Requested Address on Comm error read/write request.
Unsigned Integer
1= Invalid Password
2 = Checksum Error
3 = Block/Register Range Invalid
4 = Block/Register attempted to be accessed invalid
5 = Range of data attempted to be accessed invalid
Description
Unsigned 16 Bit
00 0101 = 07 HEX Division Code
Unsigned Integer 16 Bit
Reserved
Reserved
Reserved
Reserved
Reserved
00 1110 = 0E HEX left justified
1= Unreported Operation Record
Reserved
These bits update once every 100
mS to indicate that the
communication card is still updated
by the central TPU processor.