One 4X register at the beginning of the 4X control register groups is read only which feeds back the status of
password control which was configured via Registers 62560 through 62598 (Security Mask Control Block) or via
the Communications Configuration Screen accessible through ECP or WinECP. The register lists the six control
blocks found in the TPU2000/TPU2000R. Table 5-41 lists the Security Mask register, which reports, which of the
control blocks require password control. A status of 1 in the defined bit location allows any value to be placed in
the password field (as shown in Table 5-42). The Security mask status of what was programmed through ECP,
WinECP or Modbus Registers 62560 through 62598 may be obtained by reading Register 41409. A status of 0 in
the defined field requires the correct password to be sent as part of the control process.
Figure 5-43 illustrates the Group Blocks within the TPU2000/TPU2000R and its associated typical control register
mapping.
Command
Sequence Through
Modbus Command 16
Preset Multiple Holding Registers

Figure 5-43. Typical Control Features Available for the TPU2000 and TPU2000R

Table 5-41. Security Status Register Indicating Password Requirement

Register
Item
41409
16 Bit Unsigned
Bit 0 (lsb)
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15 (msb)
One method to perform control through the Control Block is as follows:
Write all registers other than the register associated with the "Execute Register"
Write a "1" to execute the control command.
E C
Set/Reset Outputs
41409
Description
Security Mask (Read Only, See Register 6XXXX for setup
or refer to ECP or WinECP Configuration Program)
Initiate Input (GROUP I) Password Required
Force Physical Input (GROUP II) Password Required
Force Physical Output (GROUP III) Password Required
Force Logical Input (GROUP IV) Password Required
Set/ Reset Outputs (GROUP V) Password Required
Pulse Outputs (GROUP VI) Password Required
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
41410
Initiate Inputs
Typical Definition
Force Phys. In
Execute Register
Force Phys. Out.
Password Char 1
Password Char 2
Force Log. In
Password Char 3
Password Char 4
Control Mask 1
Copy of Control Mask 1
Of a Control Block
Pulse Outputs
41457
= Read Only Register
Security Status