4.11 Transmit Configuration Settings ( 3 4 11 )
Low byte consists of bits 0 through 7.
High byte consists of bits 8 through 15.
Mode Selection Type Trip Failure
0 = Differential Trip
1 = OC Alarm
2 = Differential and OC Alarm
Mode Selection Type Demand Time Constant
0 = 5
1 = 15
2 = 30
3 = 60
Msg byte
1/1
1/2
1/3
2/1
TPU2000/2000R Modbus/Modbus Plus Automation Guide
50P-2 Timedial/delay high byte (dial *10,delay *100)
50P-2 Timedial/delay low (dial 1-10, delay 0-9.99)
150P-2 Curve Select byte (Type II)
150P-2 Pickup X byte (0.5-20, *10)
150P-2 Time Delay high byte (0-9.99, *100)
150P-2 Time Delay low byte
46-2 Curve Select byte (Type I)
46-2 Pickup Amp byte (1-12 Amp *10, 0.2-2.4Amp *50)
46-2 Timedial/delay (dial 1-10 *20, delay 0-10 *20)
51G-2 Curve Select byte (Type I)
51G-2 Pickup Amp byte (1-12 Amp *10, 0.2-2.4Amp *50)
51G-2 Timedial/delay (dial 1-10 *20, delay 0-10 *20)
50G-2 Curve Select byte (Type II)
50G-2 PickupX (0.5-20, *10)
50G-2 Timedial/delay high byte (dial *10,delay *100)
50G-2 Timedial/delay low (dial 1-10, delay 0-9.99)
150G-2 Curve Select byte (Type II)
150G-2 Pickup X byte (0.5-20, *10)
150G-2 Time Delay high byte (0-9.99, *100)
150G-2 Time Delay low byte
Disturb-2 Pickup X byte (0.5-5, *10)
Level Detector-1 PickupX (0.5-20, *10, 201=Disable)
Level Detector-2 PickupX (0.5-20, *10, 201=Disable)
spare
spare
spare
Unit Configuration byte
bit 0 : neutral tap range Wdg1 (0=1-12A, 1=0.2-2.4A)
bit 1 : phase tap range Wdg1 (0=1-12A, 1=0.2-2.4A)
bit 2 : neutral tap range Wdg2 (0=1-12A, 1=0.2-2.4A)
bit 3 : phase tap range Wdg2 (0=1-12A, 1=0.2-2.4A)
bit 4 : user definable curves
bit 5 : Reserved for frequency
bit 6 : neutral tap range Wdg3 (0=1-12A, 1=0.2-2.4A)
bit 7 : phase tap range Wdg3 (0=1-12A, 1=0.2-2.4A)
Checksum high byte
Checksum low byte
Definition
Relay Status (see command 3 4 1, msg 1/1)
Command + Subcommand = 0x4b
Total Number of Messages = 21
Wdg1 P CT Ratio high byte (1-4000)