ABB TPU2000 Technical Manual page 174

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
Register
Item
Address
3 Winding
Bit 4 = Reserved
Bit 5 = Reserved
Bit 6 = Reserved
Bit 7 = Reserved
Bit 8 = Reserved
Bit 9 = Reserved
Bit 10 = Reserved
Bit 11 = Reserved
Bit 12 = Reserved
Bit 13 = Reserved
Bit 14 = Reserved
Bit 15 = Reserved (msb)
42694
READ DATA – Trigger Flag Word 4
Bit 0 = 50N-1 (lsb)
Bit 1 = 50N-2
Bit 2 = 50N-3
Bit 3 = 51N
Bit 4 = 50P-1
Bit 5 = 50P-2
Bit 6 = 50P-3
Bit 7 = 51P
Bit 8 = 67P
Bit 9 = 67N
Bit10 = 46
Bit 11 = 27
Bit 12 = 59
Bit 13 = 79V
Bit 14 = 81S-1
Bit 15 = 81R –1 (msb)
DATE/TIMESTAMPS OF TRIGGER POINT
42695
Year
42696
Month
42697
Day
42698
Hour
42699
Minute
42700
Second
42701
Hundredths of Seconds
42702
Quarter Cycle Trigger Point
42703
Total Number of Channels
42704
Total Analog Data Channels
42705
Total Digital Data Channels
LINE FREQUENCY OF WAVEFORM
42706
Line Frequency
Description
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Unsigned Integer (16 Bits)
Neutral. Instantaneous Overcurrent Trip
Neutral. Instantaneous Overcurrent Trip
Neutral. Instantaneous Overcurrent Trip
Neutral Time Overcurrent Trip
Phase Instantaneous Overcurrent Trip
Phase Instantaneous Overcurrent Trip
Phase Instantaneous Overcurrent Trip Phase
Time Overcurrent Trip
Direct Overcurrent Trip Positive Sequence
Direct Overcurrent Trip Negative Sequence
Negative Sequence Overcurrent Trip
Undervoltage Trip
Overcurrent Trip
Recloser Lockout
Frequency Shed (First Stage)
Frequency Restore (First Stage)
Unsigned Integer 16 Bits
0-99
Unsigned Integer 16 Bits
1- 12
Unsigned Integer 16 bits
1-31
Unsigned Integer 16 Bits
0-23
Unsigned Integer 16 Bits
0-59
Unsigned Integer 16 Bits
0-59
Unsigned Integer 16 Bits
0 – 99
Unsigned Integer 16 Bits
Number of 1/4 Cycle of Trigger Point
0-255 ( Dependent on 6X Register Config)
Unsigned Integer 16 Bits
Default as 7
Unsigned Integer 16 Bits
FIXED at 7
Unsigned Integer 16 Bits
0 <=Range <= 64
Unsigned Integer 16 Bits
164