Register
Item
Address
00563:
51P-1D STATUS
00564:
51P-1D MOMENTARY
00565:
51P-2D STATUS
00566:
51P-2D MOMENTARY
00567:
51N-1D STATUS
00568:
51N-1D MOMENTARY
00569:
51N-2D STATUS
00570:
51N-2D MOMENTARY
00571:
50P-1D STATUS
00572:
50P-1D MOMENTARY
00573:
50P-2D STATUS
00574:
50P-2D MOMENTARY
00575:
50N-1D STATUS
00576:
50N-1D MOMENTARY
00577:
50N-2D STATUS
00578:
50N-2D MOMENTARY
00579:
150P-1D STATUS
00580:
150P-1D MOMENTARY
00581:
150P-2D STATUS
00582:
150P-2D MOMENTARY
00583:
150N-1D STATUS
00584:
150N-1D MOMENTARY
00585:
150N-2D STATUS
00586:
150N-2D MOMENTARY
00587:
46-1D STATUS
00588:
46-1D MOMENTARY
00589:
46-2D STATUS
TPU2000/2000R Modbus/Modbus Plus Automation Guide
(Momentary)
Winding 1 Phase Time Overcurrent Function Disabled Alarm
(Status)
Winding 1 Phase Time Overcurrent Function Disabled Alarm
(Momentary)
Winding 2 Phase Time Overcurrent Function Disabled Alarm
(Status)
Winding 2 Phase Time Overcurrent Function Disabled Alarm
(Momentary)
Winding 1 Neutral Time Overcurrent Function Disabled Alarm
(Status)
Winding 1 Neutral Time Overcurrent Function Disabled Alarm
(Momentary)
Winding 2 Neutral Time Overcurrent Function Disabled Alarm
(Status)
Winding 2 Neutral Time Overcurrent Function Disabled Alarm
(Momentary)
st
1
Winding 1 Phase Instantaneous Overcurrent Function
Disabled Alarm (Status)
st
1
Winding 1 Phase Instantaneous Overcurrent Function
Disabled Alarm (Momentary)
st
1
Winding 2 Phase Instantaneous Overcurrent Function
Disabled Alarm (Status)
st
1
Winding 2 Phase Instantaneous Overcurrent Function
Disabled Alarm (Momentary)
st
1
Winding 1 Neutral Instantaneous Overcurrent Function
Disabled Alarm (Status)
st
1
Winding 1 Neutral Instantaneous Overcurrent Function
Disabled Alarm (Momentary)
st
1
Winding 2 Neutral Instantaneous Overcurrent Function
Disabled Alarm (Status)
st
1
Winding 2 Neutral Instantaneous Overcurrent Function
Disabled Alarm (Momentary)
nd
2
Winding 1 Phase Instantaneous Overcurrent Function
Disabled Alarm (Status)
nd
2
Winding 1 Phase Instantaneous Overcurrent Function
Disabled Alarm (Momentary)
nd
2
Winding 2 Phase Instantaneous Overcurrent Function
Disabled Alarm (Status)
nd
2
Winding 2 Phase Instantaneous Overcurrent Function
Disabled Alarm (Momentary)
nd
2
Winding 1 Neutral Instantaneous Overcurrent Function
Disabled Alarm (Status)
nd
2
Winding 1 Neutral Instantaneous Overcurrent Function
Disabled Alarm (Momentary)
nd
2
Winding 2 Neutral Instantaneous Overcurrent Function
Disabled Alarm (Status)
nd
2
Winding 2 Neutral Instantaneous Overcurrent Function
Disabled Alarm (Momentary)
Winding 1 Negative Sequence Time Overcurrent Function
Disabled Alarm (Status)
Winding 1 Negative Sequence Time Overcurrent Function
Disabled Alarm (Momentary)
Winding 1 Negative Sequence Time Overcurrent Function
Disabled Alarm (Status)
Description