Metering Values (35 Registers Defined); Table 5-19. Tpu2000/Tpu2000R Metering Values - ABB TPU2000 Technical Manual

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

40176
Control Mask If Write Error
40177
Control Mask If Write Error
40178
Control Mask If Write Error
40179
Control Mask If Write Error

Metering Values (35 Registers Defined)

Metering Values are defined Table 5-19. Various data types are associated with each element. All metering
values are reported in primary units and should reflect the status as shown on the TPU2000/2000R Front Panel
Interface, ECP or WinECP metering screens. Many or the quantities are scaled, such as operating current to
denote a decimal point when read. Operate Current 40257 should be divided by 800 to obtain the decimal point
which is visible when viewing the value from the front panel.
Table 5-19. TPU2000/TPU2000R Metering Values Table
Register
Address
40257
Operate Current A
40258
Operate Current B
40259
Operate Current C
40260
Restraint Current A Winding 1
40261
Restraint Current B Winding 1
40262
Restraint Current C Winding 1
40263
Restraint Current A Winding 2
40264
Restraint Current-B Winding 2
40265
Restraint Current C Winding 2
40266
Restraint Current A Winding 3
40267
Restraint Current B Winding 3
40268
Restraint Current C Winding 3
40269
Restraint Angle-A Winding 1
40270
Restraint Angle-B Winding 1
40271
Restraint Angle-C Winding 1
40272
Restraint Angle-A Winding 2
40273
Restraint Angle-B Winding 2
40274
Restraint Angle-C Winding 2
40275
Restraint Angle-A Winding 3
40276
Restraint Angle-B Winding 3
40277
Restraint Angle-C Winding 3
40278
% Second Harmonic-A Winding 1
40278
% Second Harmonic-B Winding 1
40279
% Second Harmonic-C Winding 1
40279
% Fifth Harmonic-A Winding 1
TPU2000/2000R Modbus/Modbus Plus Automation Guide
6 = Invalid Data
7 = Settings being edited elsewhere in unit or remote edit disabled
8 = A write to one setting group attempted while actively editing
another.
9 = Breaker State Invalid
10 = Data entered is below minimum value
11 = Data entered is above maximum allowed
12 = Data entered is out of step
13 = Internal Software Error
32 = Reference Type or File Number Invalid
33 = Too many registers for Modbus Protocol
Unsigned Integer
Control Mask 1 Write Mask (MSW)
Unsigned Integer
Control Mask 1 Write Mask (LSW)
Unsigned Integer
Control Mask 2 Write Mask (MSW)
Unsigned Integer
Control Mask 2 Write Mask (LSW)
Item
Scale
Description
Factor
800
Unsigned 16 Bit
800
Unsigned 16 Bit
800
Unsigned 16 Bit
800
Unsigned 16 Bit
800
Unsigned 16 Bit
800
Unsigned 16 Bit
800
Unsigned 16 Bit
800
Unsigned 16 Bit
800
Unsigned 16 Bit
800
Unsigned 16 Bit
800
Unsigned 16 Bit
800
Unsigned 16 Bit
1
Unsigned 16 Bit
1
Unsigned 16 Bit
1
Unsigned 16 Bit
1
Unsigned 16 Bit
1
Unsigned 16 Bit
1
Unsigned 16 Bit
1
Unsigned 16 Bit
1
Unsigned 16 Bit
1
Unsigned 16 Bit
2
Unsigned High Order Byte LSB
2
Unsigned Low Order Byte MSB
2
Unsigned High Order Byte LSB
2
Unsigned Low Order Byte MSB
91