Register
Address
41666
Parameter Flag
41667
Fault Type Element
41668
Setting At Fault Event
41669
Fault Record Number
41670
Year
41671
Month
41672
Day
41673
Hour
41674
Minute
41675
Second
41676
Hundredths of Seconds 0 - 99
41677
Clear Time
41678
Winding1 Tap
41679
Winding2 Tap
41680
I operate Phase A
41681
I operate Phase B
41682
I operate Phase C
41683
I restraint Phase A-Winding 1
41684
I restraint Phase B-Winding 1
41685
I restraint Phase C-Winding 1
41686
I restraint Phase A-Winding 2
41687
I restraint Phase B-Winding 2
41688
I restraint Phase C-Winding 2
41689
2nd Harmonic Phase A-Winding 1
41690
5th Harmonic Phase A-Winding 1
41691
All Harmonic Phase A-Winding 1
41692
2nd Harmonic Phase B-Winding 1
41693
5th Harmonic Phase B-Winding 1
41694
All Harmonic Phase B-Winding 1
41695
2nd Harmonic Phase C-Winding 1
Item
unreported) record of data.
Unsigned Integer 16 Bit
Unsigned 16 Bit
00 = 87T – % Differential Alarm
01 = 87H – High Set Inst. Differential Alarm
02 = 51P-1 – Winding 1 Phase Time Overcurrent
03 = 51P-2 – Winding 2 Phase Time Overcurrent
04 = 50P-1 – 1
05 = 50N-1 – 1
06 = 150P-1 – 2
07 = 150N-1 – 2
08 = 46-1 – Neg. Sequence 1 Inst. Time Overcurrent
09 = 51P-2 – Winding 2 Phase Time Overcurrent
10 = 51G-2 – Winding 2 Ground Time Overcurrent
11 = 50P-2 – 1
12 = 50G-2 – 1
13 = 150P-2 – 2
14 = 150G-2 – 2
15 = 46-2 – Neg. Sequence 2 Inst. Time Overcurrent
16 = ECI-1 – Event Capture Initiate 1
17 = ECI-2 – Event Capture Initiate 2
18 = Through Fault
19 = Harmonic Restraint
Unsigned 16 Bit
01 = Primary Settings
02 = Alternate 1 Settings
03 = Alternate 2 Settings
Unsigned 16 Bit
(1 – 999, only last 32 kept)
2 digit 00 -99
Unsigned 16 Bit Year of Fault
1 - 12
Unsigned 16 Bit Month of Fault
1 - 31
Unsigned 16 Bit Day of Fault
00 - 23
Unsigned 16 Bit Hour of Fault
00 - 59
Unsigned 16 Bit Minute of Fault
00 - 59
Unsigned 16 Bit Second of Fault
Unsigned 16 Bit Hundredth Second of Fault Time
Unsigned 16 Bit (X 1000) seconds
Unsigned 16 Bit (X 500)
Unsigned 16 Bit (X 800)
Unsigned 16 Bit (X 800)
Unsigned 16 Bit (X 800)
Unsigned 16 Bit (X 800)
Unsigned 16 Bit (X 800)
Unsigned 16 Bit (X 800)
Unsigned 16 Bit (X 800)
Unsigned 16 Bit (X 800)
Unsigned 16 Bit (X 800)
Unsigned 16 Bit (X 800)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Unsigned 16 Bit (X 2)
Description (Multiplier if any)
st
Winding 1 Phase Inst. Overcurrent
st
Winding 1 Neutral Inst. Overcurrent
nd
Winding 1 Phase Inst. Overcurrent
nd
Winding 1 Neutral Inst. Overcurrent
st
Winding 2 Phase Inst. Overcurrent
st
Winding 2 Ground Inst. Overcurrent
nd
Winding 2 Phase Inst. Overcurrent
nd
Winding 2 Ground Inst. Overcurrent
118