Physical Output Block (Single Bit Data) - 16 Discrete Coils (8 Elements Defined); Logical Output Block (Two Bit Data With Momentary Change Detection); Table 5-2. Physical Output Contact Mapping Defined; Table 5-3. Momentary Change Detect Data Definition - ABB TPU2000 Technical Manual

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
Register
Address
3
00838:
PWatt3
3
00839:
OCA Gnd
3
00840:
OCA Gnd
Physical Output Block (Single Bit Data) – 16 Discrete Coils (8 Elements Defined)
Output status is described in Table 5-2. The state of the addresses 00257 through 00272 follow the state of the
physical output hardware contacts located at the rear screw terminals of the relay. It should be noted that some
of the Physical Output contact status information is not available in the TPU2000R. Table 5-2 notes the elements,
which are undefined in the TPU2000R. The TPU2000R has six physical output contacts, which are map-able via
ECP software. The TPU2000R has a single dedicated physical output contact defined as TRIP. The TPU2000
has seven map-able physical output contacts (1 through 7) and a dedicated TRIP contact. The status of the
element mirrors that of the physical contact and that reported through the TPU2000/2000R front panel interface of
through the ECP or WinECP configuration program.

Table 5-2. Physical Output Contact Mapping Defined

Discrete Address
00257:
00258:
00259:
00260:
00261:
00262:
00263:
00264:
00265:
00266:
00267:
00268:
00269:
00270:
00271:
00272:

Logical Output Block (Two Bit Data with Momentary Change Detection)

Modbus does not support features commonly required within the utility industry. However, the protocol may easily
be adapted to support features required. It is most important that no event is to be missed by a polling host when
a device is not accessed. To this end, a feature has been developed which ensures that the status of the data
change is always reported. Table 5-3 lists the Momentary Logical Output Mapping.

Table 5-3. Momentary Change Detect Data Definition

Register
Address
00001
DIFF
00002
SELFCHECK
ALARM
00003
87T
00004
87H
00005
2HROA
00006
5HROA
00007
AHROA
00008
TCFA
Item
Item
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
OUT7
OUT 6
OUT5
OUT4
OUT3
OUT2
OUT1
TRIP
Item
Differential Trip Contact Energized
Self Check Alarm Energized
Harmonic Restrained % Differential Trip Alarm Energized
Unrestrained High Set Instantaneous Differential Trip Alarm Energized
nd
2
Harmonic Restraint Alarm Energized
th
5
Harmonic Restraint Alarm Energized
All Harmonics Restraint Alarm (2
Trip Circuit is Open Fail Alarm Energized
Winding 3 Positive 3 Phase kWatt Alarm Energized
Ground Overcurrent Alarm Energized
Ground Overcurrent Alarm Energized
Description
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Physical Output Contact 7
Physical Output Contact 6
Physical Output Contact 5
Physical Output Contact 4
Physical Output Contact 3
Physical Output Contact 2
Physical Output Contact 1
Breaker Trip Physical Output Contact
Description
nd
through 11th Harmonic) Energized
Description
58