3.
The default list corresponds to the Logical Input mapping of Logical Inputs (hereto referred as LI) as
illustrated in Table 5-47.
4.
If one would wish to change the relay protective function element mapped to the specific LI, depress
the "ENTER" key. The display in Figure 5-55 shall result.
5.
The user would then scroll down the list and highlight the element desired to be mapped to the
specific LI within the edited list.
6.
Depress the "ENTER" key to map the selected element into the table.

Table 5-47. ECP Default Correlation to Forced Logical Input Bit Map

FLI
Description
Number
FLI 01
3 Phase % Diff. Current Control
FLI 02
3 Phase Inst. Differential Current
Control
FLI 03
Winding 1 Phase Time
Overcurrent Control
FLI 04
Winding 2 Phase Time
Overcurrent Control
FLI 05
Winding 1 Neutral Time
Overcurrent Control
FLI 06
Winding 2 Ground Time
Overcurrent Control Winding 2
FLI 07
Phase Instantaneous Level 1
Enable Winding 1
FLI 08
Phase Instantaneous Level 1
Enable Winding 2
FLI 09
Neutral Instantaneous Level 1
Enable Winding 1
FLI 10
Ground Instantaneous Level 1
Enable Winding 2
TPU2000/2000R Modbus/Modbus Plus Automation Guide

Figure 5-54. ECP Default Logical Input List

User
Name
87 T
87H
51P-1
51P-2
51N-1
51G-2
50P-1
50P-2
50N-1
50G-2
FLI
Description
Number
FLI 17
Alternate Settings 1 Enable
FLI 18
Alternate Settings 2 Enable
FLI 19
Event Capture Initiate 1
FLI 20
Event Capture Initiate 2
FLI 21
Waveform Capture Initiate
FLI 22
Differential Trip Output
Contact Enable
FLI 23
Sudden Pressure
FLI 24
Trip Coil Monitor Enable
FLI 25
User Logical Input 1
FLI 26
User Logical Input 2
User
Name
ALT 1
ALT 2
ECI 1
ECI 2
WCI
TRIP
SPR
TCM
ULI 1
ULI 2
147