Procedural Considerations

Table 7 DE Calibration - Apply Values

Overview
of
Objectives:
Page 34
DE Calibration - Apply PV values to Set LRV and Set URV
Manually set the Process Variable input to 0%, and apply this value to Set LRV;
Manually set the Process Variable input to 100%, and apply this value to Set URV.
NOTE:
This procedure applies to DE Transmitters operating in DE Mode as well as to those
operating in Analog (current) Mode.
On the DE MAIN MENU,
select the
Calibration
button.
34-ST-25-20 MC Toolkit User Manual
In the Apply Values group,
select the
button.
Set LRV
The popup message at right
appears.
Note:
The value of the Input
indicated in this message
updates only when the
popup message is called
up.
To update this value,
select the
button, and
No
again select the
Set LRV
button in the
CALIBRATION
display.
Release 3
9/06