Table 13 Honeywell HART Calibration - LRV and URV
Correct
Select
Corr. Input LRV
LRV
(St3000
and
STT25H)
Connect precision input
pressure source, and set to
the desired Lower Range
Correct
Select
Correct Input URV
URV
(ST3000
and
STT25H)
Connect precision input
pressure source, and set to
the desired Upper Range
Value.
Release 3
9/06
Ensure that pressure input
source is correct and is not
varying.
Then, to set the LRV
parameter in the transmitter
to the applied value, select
OK
Value.
.
Ensure that pressure input
source is correct and is not
varying.
Then, to set the LRV
parameter in the transmitter
to the applied value, select
OK
34-ST-25-20 MC Toolkit User Manual
MC Toolkit Software with Honeywell HART Transmitters
in the pop-up window.
in the pop-up window.
The LRV value is stored in
the transmitter.
The URV value is stored in
the transmitter.
53