Procedural Considerations
Table 17 Honeywell HART Calibration - Apply Values
•
Overview
Manually set Process Variable input to 0%, and apply this value to Set LRV (output) at
of
4 MA.
Objectives
•
Manually set Process Variable input to 100%, and apply this value to set URV (output)
at 20 mA.
(Adjust
This function uses actual
and View
process values to calibrate
Process
input of LRV and URV.
Variable
input value
Physically observe the value
at LRV.)
of the Process Variable, and
adjust it manually to the
desired LRV value.
Select the
button on the Calibration
menu; the display at right
appears.
Page 58
Honeywell HART Calibration - Apply Values
Apply Values
34-ST-25-20 MC Toolkit User Manual
Select the Send button.
This popup message
appears.
Release 3
9/06