Messages and Diagnostic Codes
Error code 12: URV too low
Error code 13: Parameter out of limits
Error code 14: Span Too Small
Error Code 14: Warning: New LRV pushed
URV over Sensor Limit
Error code 16: Access restricted
Error code 32: Device is Busy!
Error Code 64: Command not implemented in
the Transmitter!
Error on Burst Response!
HART Communication Error!
Invalid command number from the Transmitter.
Please make sure that another secondary
master is not on the network!
Manufacturer Code not be found
No device found!
Non primary variable out of limits
Parity Error!
Overrun Error!
Framing Error!
Checksum Error!
Reserved Field Error!
Receive Buffer Overflow!
Primary variable out of limits
Undefined Response code for the command
associated with the current operation!
Page 70
HART MESSAGES
URV too low or out of range.
Parameter is out of the valid range.
Span Too Small
The new URV has caused the URV to go over the sensor limits.
Access to the parameter is not allowed.
Device is currently busy; try command again.
Action is not supported by the transmitter.
The burst message contained a communications error.
MC Toolkit detected a communications error in the HART
message.
The HART protocol supports only one secondary master on the
network.
Manufacturer Code not be found
No HART devices could be found on the network.
Process applied to the non-primary variable is outside the
operating limits of the field device.
Bit 6 on first response code byte set. MC Toolkit detected a
communications error in the HART message.
Bit 5 on first response code byte set
Bit 4 on first response code byte set. MC Toolkit detected a
communications error in the HART message.
Bit 3 on first response code byte set
Bit 2 on first response code byte set
Bit 1 on first response code byte set
Process applied to the primary variable is outside the operating
limits of the field device.
Response code (First byte) value 1 is returned from the
transmitter. This response value is undefined in the currently
supported HART devices
34-ST-25-20 MC Toolkit User Manual
Release 3
9/06