Procedural Considerations
Input Calibration (De Transmitters) - Correct Input (Zero), LRV, URV; Reset Corrects
Set-Up On Bench
A typical bench set-up is shown at right.
Connect the MC Toolkit as indicated, and
establish communication with the
transmitter.
For these procedures, components in the
current loop are not critical, provided that
they support reliable communication
between the transmitter and the MC Toolkit.
If a Honeywell ST 3000 Pressure
Transmitter is being calibrated, positioning
(leveling) is important, because the meter
body contains fluids that can affect zero
sensing.
Enter
From the DE MAIN MENU, select
(configure)
DE CONFIGURE display.
values for
a. Use the
LRV and
URV
b. Using the keyboard, enter the desired LRV and URV
c. Select the Send button to copy all newly entered values to
Page 26
to select the appropriate Engineering
PV Units
Units.
values.
the transmitter. When the copy operation is complete,
Send will be displayed in half intensity.
34-ST-25-20 MC Toolkit User Manual
to call up the
Configure
Release 3
9/06