Calibrate
The 20 mA calibration
20 mA
display appears.
Output
Again, observe the resulting
(Example 1)
mA output on the connected
meter.
Calibrate
20 mA
Output
(Example 2)
The new value is observed
as 5.00 V (20.00 mA),
which is entered into the
Meter Value
Release 3
9/06
Honeywell HART Calibration - D/A Trim
In the example at right,
meter indication of 4.97 V
is converted to 19.80 mA
and entered into the
Value
Select
entered value to the
transmitter output
algorithm.
In the example at right, the
corrected value was 5.02 V
(20.08 mA).
This new value is entered
and
Send
When the Send button is
selected, this display
appears.
field.
34-ST-25-20 MC Toolkit User Manual
MC Toolkit Software with Honeywell HART Transmitters
Meter
field.
to copy the
Send
is selected again.
The calibration is
completed, but the 20.00
mA calibration value is
retained until
in the
OK
popup message is selected.
When the
button is
OK
selected, the output current
goes back to tracking the
input value, and the popup
message disappears.
Select
to return to the
Back
menu.
CALIBRATION
57