Honeywell MC ToolKit User Manual page 67

Communications tool
Table of Contents

Advertisement

Apply
Select the OK button. The display at right
Values:
appears.
LRV
The Current Applied Process Value field
shows the value of the Process Value. A
new sample of the input level is displayed
each time the user selects the Read New
Value button.
Adjust the process variable to the desired
value while repeatedly selecting the Read
New Value button to monitor and verify
the input value.
(Write
When the Process Variable
input value
is stabilized at the desired
as LRV.)
input level, select the Set
New Value button.
The popup at right appears.
Select the OK button to
write the input value as the
LRV calibration value; and
the popup message box will
disappear.
(Adjust
Select the 20 mA button.
and View
The popup at right appears.
Process
Variable
input value
at URV.)
Release 3
9/06
Honeywell HART Calibration - Apply Values
This display at right is the
same one used for applying
PV input as LRV value.
Adjust the PV input to the
desired URV level while
using the Read New
Value button for
monitoring.
34-ST-25-20 MC Toolkit User Manual
MC Toolkit Software with Honeywell HART Transmitters
59