Procedural Considerations
Input Calibration (De Transmitters) - Correct Input (Zero), LRV, URV; Reset Corrects
Correct
Select the
Input at
button. This message appears.
LRV
(ST 3000)
Adjust the PV input pressure
to the exact value of the LRV
entered in the DE
CONFIGURE display.
Correct
Select the
Input at
button. This message appears.
LRV
(STT 3000)
Correct
Select the
Input at
button. This message appears.
URV
(ST 3000)
Correct
Select the
Input at
button. This message appears.
URV
(STT 3000)
Page 28
Select the
Correct LRV
message appears.
Observe the input pressure
at the applied value; when
it is stable, select the
button.
Adjust the input
Correct LRV
temperature to the exact
value of the LRV entered in
the DE CONFIGURE
display.
Adjust the PV input
Correct URV
pressure to the exact value
of the URV entered in the
DE CONFIGURE display.
Select the
Adjust the input
Correct URV
temperature to the exact
value of the URV entered
in the DE CONFIGURE
display.
34-ST-25-20 MC Toolkit User Manual
button; this
When the transmitter has
OK
completed the LRV
correction, this message
appears.
Select
acknowledge.
OK
Select the
message appears.
Select the
acknowledge
When the transmitter has
completed the URV
correction, this message
appears.
Select
button.
OK
acknowledge.
Select the
message appears.
Select the
to
OK
button; this
OK
button to
OK
to
OK
button; this
OK
button to
OK
acknowledge
Release 3
9/06