Table 15 Honeywell HART Calibration - Loop Test

Loop Test
This function verifies the
integrity of the physical
components of analog
output loop current in a
process application
To observe output current
levels, connect a voltmeter
or current meter into the
current loop.
Observe the meter, and
select
Yes
message to command the
transmitter to go to the
selected current level.
To return to the input-
dependent current level,
select
Clear Output
popup message appears.
Release 3
9/06
Honeywell HART Calibration - Loop Test
If the
in the popup
selected before using the
Clear Output command, the
message at right appears.
To go back to the
Calibration Menu, select
OK
; this
Clear Output
select the
34-ST-25-20 MC Toolkit User Manual
MC Toolkit Software with Honeywell HART Transmitters
button is
Back
in the popup, select the
button, then
button.
Back
Select the desired current
level, then select
.
Set Output
55