Honeywell Properties (°C Or °F) - Honeywell EXCEL5000 OPEN XILON User Manual

Handheld tool
Table of Contents

Advertisement

XILON HANDHELD TOOL - USER GUIDE
EN2B-0214GE51 R0503
You can switch digital outputs and analog outputs back and forth between the
"automatic" and the "manual" modes using the <ENTER> key.
"Manual" mode means that the value is written to nviAoManOvr or nviDoManOvr.
"Automatic" mode means that INVALID is written to nviAoManOvr or nviDoManOvr.
NOTE: The mode and value can also be changed using LonMaker for Windows if
you write to the correct NV, e.g. nviAoManOvr[1,50%]. An I/O which is set
to the manual mode is fixed until it is changed using XILON or until any
other tool/device writes on the override NV (nviAoManOvr or
nviDoManOvr).
The Excel Smart I/O LonWorks service LED will flash once (three seconds ON and
1 second OFF) if a module has a value in the manual mode. After a power failure,
the Smart I/O module will re-establish the manual value.
When set to "°C", XILON displays all temperature values in Celsius. Using this
function, all temperature values can be switched to the Fahrenheit scale.
30
Honeywell Properties (°C or °F)

Advertisement

Table of Contents
loading

Table of Contents