MAN0604_Issue 09_02-2013
2110M8030
3.1.4 Transmitter Unit Configuration
Caution:
Do not change either Relay or 4-20mA link setting while unit is powered up.
The following information specifies the unit configuration options.
Relays
Links J1, J2 and J3 set the contact operation for the Fault, Alarm 1 and Alarm 2 relays respectively.
J1 (Fault relay - normally energised)
Normally open (default)
J2 and J3 (Alarm 1 and 2 Relays - normally de-energised)
Normally open (default)
Note: Relay states shown are the shelf state. Relay contacts are rated at 100mA (min), 2A (max),
30Vdc non-inductive*. HIGHER VOLTAGES MUST NOT BE USED
(* UL specification: 28Vdc, 1A)
3. inSTAllATiOn
J4
J5
Fault Alarm Alarm
J1 J2 J3
29
1
2
J1
J2
J3
Normally closed
Normally closed
Apex