Configure 4-20mA
Provides the means to configure the values for the 4-20mA signal output settings. Three settings are
available:
Inhibit
Warning
Overrange
Caution: When compliance with the ATEX performance standard is required the warning and inhibit
current shall not be configured to a value between than 3.1mA and 4.9mA
Once configured to a new value, the new value is output when the corresponding states occur.
When the Warning current is configured to be greater than 4mA the output pulses to the configured
Warning current for approximately 1 second every 10 seconds.
4. OPERATION
Change Cartridge
ok
Change Cartridge screen
Change
cartridge
ok
Checking
Success?
ok
Calibration Menu
Value 1mA to 4mA, default is 1mA.
Value 1mA to 6mA, default is 3mA.
Value 20mA to 21.5mA, default is 21mA.
Follow cartridge
change
instructions
See Section 5