Toshiba GR-200 Series Instruction Manual page 549

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Optional communication
(ii)
The table below shows optional modules, used for such as time synchronization, data transfer
of Modbus and IEC60870-5-103 connection.
Table 5.5-2 Optional modules for COM#3
Type
IRIG-B
Connector
PCB connector
Medium
Shielded twist pair
Time
Usage
synchronization
IRIG-B000
A1
B1
SIG
A2
Symbol
DISUSE
B2
DISUSE
A3
B3
GND
IRIG-B000
IRIG-B000 module is used to receive the digital signal generated with an external clock; the
signal is in conformity to serial IRIG-B000 format. Note that the IRIG-B000 module is able
to receive digital signal (TTL) only (i.e., the reception of AM signal is not applicable). This
module is isolated using a photo coupler; the user should note A2 and B2 connectors are not
used. The peak value of IRIG-B000 signal should be greater than 3.5 volts; the IRIG-B000
module has the input resistor (about 3k ohm). Thus, the terminal resistor can be required
when the IRIG-B000 signal is delivered for several devices; the value of the terminal resistor
depends on the number of deliveries and the performance of the external clocks. For setting
of time synchronization, see Chapter 5.8.
a. View from connector edge
RS485
RS485 is used for communication in the IEC60870-5-103 and Modbus. It should be connected
RS485
PCB connector
Shielded twist pair
Data transfer over
Modbus, or
IEC60870-5-103
RS485
A1
B1
COM-A
A2
B2
COM-B
A3
B3
COMM
Top
PCB connector
A1
B1
A2
B2
A3
B3
Bottom
Figure 5.5-3 IRIG-B000 module
- 530 -
100Base-TX/
Fiber optic
ST type
Fiber optic(GI)
Shielded twist pair
Data transfer over
GR-TIEMS
IEC60870-5-103
Fiber Optic
RX
0
TX
A1
GND
B1
A2
(Disuse)
B2
(Disuse)
A3
SIG
B3
b. Port circuit
6F2T0200 (0.15)
1000Base-T
RJ45
GRE200 (1,2)