Supervision of ECC on memory (ECC error)
10.2.4
Error-correcting code memory (ECC memory) is verified at any time.
Error level
(i)
The error level has been set at level 1 (Serious error) in the automatic supervision. Checking
is carried out at any time. If an error is detected, the IED automatically restarts the operation.
The supervision function runs at the CPU module
when the error is solved.
Note: The CPU module is discussed in Chapter
1
and communication module: Signal processing
Error message
(ii)
When detecting an error, the error message will be shown on the LCD screen. LED will be lit
up.
Table 10.2-7 Error messages provided by the supervisor in CHK_ECC
Message and level
CP*_ (ECC) error
Error level
Table 10.2-8 Detailed information in Hexadecimal in CHK_ECC
Display
area
Top
row
Middle
Number of detections of bit errors
row
Bottom
Number of rewriting failure occurred
row
after the correction of single bit error
Error in the ECC is detected on the following module instructed
with "CP*_" as follows:
CP1M:
Serious error (Level 1)
Meaning of the detailed information
Left column
err_cnt value
- 683 -
. The error message will be cleared promptly
1
Technical description: Signal processing
(→p. 528)
Meaning of the information
CPU module
Right column
Error address
Address for rewriting failure occurred after
the correction of single bit error
ECC status
00000001: Completion of correction
00000002: Failure of correction
00000004: Detection of single error
00000008: Detection of several errors
00000010: Writing failure of data correction
6F2T0200 (0.15)
.
GRE200 (1,2)