10.2.30 Supervision of link redundant entity (LRE error)
LRE operation is checked and the error message is screened when the LRE does not operate
correctly or wrong data is written in the FPGA.
†Note: see Chapter
Error level
(i)
Error level has been set at level 1 (Serious error; default), but the user can change it with
setting [CHK_LRE:LVl]. Remember that the user needs to set On for setting [CHK_LRE:Sw].
Error message
(ii)
When detecting an error, the error message will be shown on LCD screen. LED will be lit up.
Table 10.2-59 Error messages provided by the supervisor in CHK_LRE
Message and level
CP*_(LRE) error
Error level
Table 10.2-60 Detailed information in Hexadecimal in CHK_LRE
Display
area
00000001: Type error in FPGA
Top
00000002: Port state error in redundant module
row
00000004: Mode error in redundant module
Middle
(No information is displayed)
row
Bottom
(No information is displayed)
row
Communication Protocol: LAN operation
Meaning of the information
Detection of the failure in the LRE instructed with "CP*_" as
follows:
CP1M: CPU module
Serious error (Level 1)
Meaning of the detailed information
Left column
- 710 -
6F2T0200 (0.15)
(→p. 741).
Right column
FPGA type number in CP1M
(No information is displayed)
(No information is displayed)
GRE200 (1,2)