judgement processes, and Mot-STPH is operating based on generation of these
"judgment result".
Motor status Start-up
Count of the number of
times the motor has
started within 1 hour
Mot-STPH operation
Result of judgement in 1st
Result of judgement in 2nd
Result of judgement in 3rd
Result of judgement in 4th
Result of judgement in 5th
Result of judgement in 6th
Result of judgement in 7th
Result of judgement in 8th
Figure 2.28-17 Timing chart example about Mot-STPH operation
Scheme logic
The scheme logic of the restart inhibit function including the starts per hour function
will be illustrated in Figure 2.28-18. In order to block the output of the starts per hour
function operational signal, the user should input some signal at PLC connection point
[Mot-STPH_BLOCK].
Table 2.28-12 Settings corresponded to the Mot-STPH
Setting items
Mot-STPH-EN
Mot-STPH-Num
Emergency start function (Canceling to block CB closing)
(ii)
In case of emergency, it is possible to allow closing CB, even if the restart inhibit function has
been operated already. It can be achieved, when a signal is generated at PLC connection pint
[Mot-EMR_START].
Therefore, the emergency start function can be constructed by connecting an emergency signal
inputted to IED via binary input circuit (BI) to this PLC connection point.
1 hour (1st)
1
2
1 hour (2nd)
1
2
1
Range
Unit
Off / On
-
Starts per hour function enable
1 - 60
-
Limit number for Starts per hour
- 341 -
1 hour (3rd)
2
3
1
1 hour (4th)
2
3
1 hour (5th)
1
2
1 hour (6th)
1
Contents
6F2T0200 (0.15)
Timing of motor start-up
2
3
1 hour (7th)
1
2
1 hour (8th)
1
Default
Off
60
GRE200 (1,2)