Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Relay OC G
OC G
Fault current
Unfaulted current
CO-OC element
Fault current
Unfaulted current
Relay OC R
OC R
Fault current
Unfaulted current
pick-up and drop-off of fault current using an over current element (CO-OC) or an earth fault
element (OC-EF), which are arranged within the ARC function as shown in Figure 2.22-17.
The user must set the thresholds of the CO-OC and CO-EF relays using settings [CO-OC] and
[CO-EF], respectively. To engage the coordination feature, set the [ARCCO-OCEN] or [ARCCO-
EFEN] to On, the switches of which are shown in Figure 2.22-18.
Current
Inflow
DT G
(1)
1st trip
Current
Inflow
ARC SHOT1
Current
Inflow
DT R
(1)
1st trip
ARC SHOT1
Figure 2.22-17 Coordination of shot number performed
The matching of shot numbers is achieved by distinguishing a different duration for the
DT G
IDMT G
(2)
2nd trip
The CO-OC element detects the time duration between
the pick-up and drop-off of fault current so that the 'ARC
COORD' signal can be generated.
ARC COORD
ARC SHOT2
ARC SHOT3
Consequently, ARC SHOT3 and ARC SHOT4
DT R
IDMT R
(2)
2nd trip
3rd trip
ARC SHOT2
ARC SHOT3
- 251 -
IDMT G
(3)
3rd and 4th tripping are not
performed.
ARC COORD
ARC SHOT4
are generated hypothetically.
IDMT R
(3)
4th trip
ARC SHOT4
6F2T0200 (0.15)
(4)
(4)
GRE200 (1,2)