Setting of UV_MV (Function ID: 470181)
Setting device
TUV4
IDMT
UV4
UV4-DPR
UV4-TMS
TUV4R
ORG
UV4
UV4-DPR
UV4-TMS
TUV4R
Output
UV4-VTFBlk
UV4-UseFor
Test setting(Function ID: 470181)
Setting device
Test option
UV-Test
Range
Unit
0.00 - 300.00
s UV4 operating delay time (in DT mode)
5.0 - 130.0
V UV4 threshold
100 - 120
% UV4 drop-out/pick-up ratio
0.010 - 100.000
- UV4 time multiplier (in IDMT mode)
0.0 - 300.0
s UV4 definite time reset delay
5.0 - 130.0
V UV4 threshold
100 - 120
% UV4 drop-out/pick-up ratio
0.010 - 100.000
- UV4 time multiplier (in ORG mode)
0.0 - 300.0
s UV4 definite time reset delay
Non / Block
- UV4 operation block by VTF
Trip / Alarm
- UV4 used for trip or alarm
Range
Unit
Off / On
- Not to execute UV block function
- 151 -
Contents
Contents
6F2T0200 (0.15)
Default
Note
1.00
60.0
100
1.000
0.0
60.0
100
1.000
0.0
Non
Trip
Default
Note
Off
GRE200 (1,2)